Error codes – Rockwell Automation 2080-LC20-20QBBR Micro820 20-point Programmable Controllers User Manual User Manual

Page 121

Advertising
background image

Troubleshooting Appendix B

Rockwell Automation Publication 2080-UM005A-EN-E - December 2013

113

Error codes

This section lists possible error codes for your controller, as well as recommended
actions for recovery.

If an error persists after performing the recommended action, contact your local
Rockwell Automation technical support representative. For contact information,
go to

http://support.rockwellautomation.com/MySupport.asp

Indicator
Behavior

Probable Error

Probable Cause

Recommended Action

All indicators off

No input power or

power supply error

No line power

Verify proper line voltage and connections to the controller.

Power supply

overloaded

This problem can occur intermittently if power supply is overloaded when

output loading and temperature varies.

Power and FAULT

indicators on solid

Hardware faulted

Processor hardware

error

Cycle power. Contact your local Allen-Bradley representative if the error

persists.

Loose wiring

Verify connections to the controller.

Power on with

solid indicator and

FAULT indicator

flashing

Application fault

Hardware/software

major fault detected

For error codes and status information, refer to the Connected Components

Workbench online Help

Power on with

solid indicator and

FAULT indicator

flashing

Operating system fault

Firmware upgrade

unsuccessful

See

Flash Upgrade Your Micro800 Firmware on page 121

.

Advertising