Using microSD Cards

triggered and configured through the Connected Components Workbench, the
2080-REMLCD module, and the ConfigMeFirst.txt file in the microSD card.

Backup and restore can only occur when the controller is in PROGRAM mode.
On controller powerup, restore automatically occurs if the Load Always or Load
on Memory Error option has been configured in Connected Components
Workbench.

The microSD card stores the controller password in encrypted format. When the
password is mismatched, the contents of the microSD card is not restored on the
controller.

Backup and restore can be configured to trigger through the following ways:

IMPORTANT

To learn about restore and backup using the 2080-REMLCD module, see

Using the Micro800 Remote LCD on page 63

.

To learn about restore and backup using the Connected Components
Workbench, refer to the software Online Help.

IMPORTANT

For Micro800 controllers that support microSD cards, IP protection of
user project can only be achieved through the POU password protection
mechanism in Connected Components Workbench (Developer Edition)
and NOT via Controller Lock feature.

Method

Backup

Restore

Online with Connected

Components Workbench

Yes

Yes

2080-REMLCD

Yes

Yes

Project configuration on

memory card at powerup

No

Load Always and/or Load on

Memory Error options

ConfigMeFirst.txt at

powerup

Yes

(Through the [BKD] command)

Yes

(Through the [RSD] command)