Chapter 4

Wire Your Controller

5.

In Connected Components Workbench, go to Embedded I/O
configuration page. Change the Gain parameter value for Input 00 to 98.

No changes are required to the Offset parameter value.

6.

Repeat the same steps to calibrate all the other analog input channels.

Analog Input to Transmitters

Analog Output

The analog output can support voltage function as shown in the following
illustration.

Power
Supply

+

2-wire Transmitter

+

Supply

GND

Signal

Controller

I-00, I-01, I-02 or I-03

-DC24

+

Controller

I-00, I-01, I-02 or I-03

-DC24

Supply

Signal

+

Controller

I-00, I-01, I-02 or I-03

-DC24

+

+

3-wire Transmitter

4-wire Transmitter

Power
Supply

Power
Supply

46257

Voltage
Load

+DC24

-DC24

VO-0

-DC24

NU

CM0

O-00

CM1

CM2

O-01

O-03

O-02

1

2

3

4

5

6

7

8

9

10

11

12

O-04

CM3

O-06

O-05

13

14

15

16

46256