Rockwell Automation Publication 2080-UM005A-EN-E - December 2013

45

Communication Connections Chapter 5

Configure Modbus RTU

1.

Open your Connected Components Workbench project. On the device
configuration tree, go to the Controller properties. Click Serial Port.

Embedded

Responses

To use embedded responses, choose Enabled

Unconditionally. If you want the controller to use

embedded responses only when it detects embedded

responses from another device, choose After One

Received.
If you are communicating with another Allen-Bradley

device, choose Enabled Unconditionally. Embedded

responses increase network traffic efficiency.

After One

Received

NAK Retries

The number of times the controller will resend a

message packet because the processor received a NAK

response to the previous message packet transmission.

3

ENQ Retries

The number of enquiries (ENQs) that you want the

controller to send after an ACK timeout occurs.

3

Transmit Retries

Specifies the number of times a message is retried after

the first attempt before being declared undeliverable.

Enter a value from 0…127.

3

ACK Timeout

(x20 ms)

Specifies the amount of time after a packet is

transmitted that an ACK is expected.

50

CIP Serial Driver Parameters