Rockwell Automation Publication 2080-UM005A-EN-E - December 2013

Appendix E

Modbus Mapping for Micro800

Parameter numbers listed in this section are for a PowerFlex 4M and will be
different if you are using another PowerFlex 4-Class drive.

• Connect the 1203-USB to the PowerFlex Drive and to the Computer.
• Launch Connected Components Workbench, Connect to the Drive and

set parameters.

To configure PowerFlex 4M, perform the following steps:

1.

Double-click the PowerFlex 4M if it is not already open in Connected
Components Workbench.

2.

Click Connect.

3.

In the Connection Browser, expand the AB_DF1 DH+ Driver.
Select the AB DSI (PF4 Port) and click OK.

4.

Once the Drive has connected and been read in, select the Start up wizard
and change the following items. Select Finish to save the changes to the
drive.
• Select the Comm Port as the Speed Reference. Set P108 [Speed

Reference] to 5 (Comm Port).

• Set Start Source to Comm Port. Set P106 [Start Source] to 5 (Comm

Port).

• Defaults for the remaining Inputs
• Accept Defaults for the remainder and click Finish.

5.

Select Parameters from the Connected Components Workbench window.

Parameter Name

Parameter Number

4M

4

40

40P

400

400N

400P

Start Source

P106

P36

Speed Reference

P108

P38

Comm Data Rate

C302

A103

C103

Comm Node Addr

C303

A104

C104

Comm Loss Action

C304

A105

C105

Comm Loss Time

C305

A106

C106

Comm Format

C306

A107

C102