Rockwell Automation 2080-LC20-20QBBR Micro820 20-point Programmable Controllers User Manual User Manual

Page 76

Advertising
background image

68

Rockwell Automation Publication 2080-UM005A-EN-E - December 2013

Chapter 8

Using the Micro800 Remote LCD

The controller limits certain operations according to controller mode, as shown
in the following table.

View and Edit Variable Values through the Remote LCD

Go to the 2080-REMLCD configuration window in Connected Components
Workbench. Click LCD Variables and select which variables you would like to
edit through the Remote LCD.

Main Menu Items

Menu Item

Description

I/O Status

Shows the status of the local I/O.

Mode switch

Change the mode switch selection.

Variables

View and change the data value of a variable. Using Connected Components

Workbench software, you can specify which variables in the program can be

viewed and edited through the 2080-REMLCD module.
See

View and Edit Variable Values through the Remote LCD on page 68

.

Security

Activate, deactivate and change password protection.

Advanced Set

System Info

View system information such as operating

systems series and firmware revision.

Fault Code

View controller fault code information.

LCD Setup

Adjust LCD contrast, backlight color and

push button.

Clock Setup

The real-time clock and daylight saving time.

Language

Change menu language to French, Italian,

Spanish, and Chinese.

Analog Calibration

Configure calibration parameter of embedded

analog inputs.

PwrUp Behavior

Configure controller mode on powerup.

Memory Card

Access the microSD card.

ENET Cfg

View and change the Ethernet port configuration.

Operational Limit on 2080-REMLCD

Operation

PROG Mode

RUN Mode

Variable Edit

NO

YES

Analog Calibration

YES

NO

Controller → Memory Card

YES

NO

Memory Card → Controller

YES

NO

Others

YES

YES