82

Rockwell Automation Publication 2080-UM005A-EN-E - December 2013

Chapter 9

Using microSD Cards

IMPORTANT

Datalog Function Block Execution

There are three possible states for the Datalog function block: Idle,

Busy and Complete (which includes Complete with Succeed and

Complete with Error).

For one Datalog function block execution, the typical status starts

from Idle, then Busy and finishes with Complete. To trigger another

function block execution, the status needs to go back to Idle first.

Idle status changes to Busy status only when Enable input signal is in

rising edge. Complete status enters Idle status when Enable input

signal is Disable status only.

TSEnable and CfgId input parameters are only sampled at Enable

input parameter's rising edge when a new function block execution

starts. During function block execution, the input parameters of

TSEnable and CfgId are locked and any changes are ignored.

When execution completes, the status changes from Busy to

Complete. At this stage, if input Enable is False, status changes to

Idle after indicating Complete for exactly one scan time. Otherwise

function block status is kept as Complete until input Enable changes

to False.

The datalog file can only be created by the DLG instruction block.

Connected Components Workbench can only upload and delete the

datalog file.

There are separators in between every data variable in the data file

which is defined during configuration in Connected Components

Workbench.

See

Supported Data Types for Datalog and Recipe Function Blocks on

page 82

.

Data variable values are sampled when datalogging function block is

in Busy state. However, datalogging file is only created when

datalogging function block is in Complete state.

Supported Data Types for Datalog and Recipe Function Blocks

Data Type

Description

Example format in output
datalog file

BOOL

(1)

Logical Boolean with

values TRUE and FALSE

0: FALSE

1: TRUE)

SINT

Signed 8-bit integer value -128, 127

INT

Signed 16-bit integer

value

-32768, 32767

DINT

Signed 32-bit integer

value

-2147483648, 2147483647

LINT

Signed 64-bit integer

value

-9223372036854775808, 9223372036854775807

USINT(BYTE)

Unsigned 8-bit integer

value

0, 255

UINT(WORD)

Unsigned 16-bit integer

value

0, 65535

UDINT(DWORD) Unsigned 32-bit integer

value

0, 4294967295

ULINT(LWORD)

Unsigned 64-bit integer

value

0, 18446744073709551615