Appendix B

Troubleshooting

116

Rockwell Automation Publication 2080-UM005A-EN-E - December 2013

OxF019

An unexpected software error occurred due to memory or

other controller resource issue.

Perform one of the following:

Download the program using Connected Components Workbench
software.

Transfer the program using the memory module restore utility or the
microSD card.

4. If the fault persists, contact your local Rockwell Automation technical

support representative. For contact information, see:

http://support.rockwellautomation.com/MySupport.asp

.

0xF020

The base hardware faulted or is incompatible with the

Micro800 controller’s firmware revision.

Perform one of the following:

Upgrade the Micro800 controller’s firmware revision using ControlFlash.

Replace the Micro800 controller.

Contact your local Rockwell Automation technical support representative
for more information about firmware revisions for your Micro800
controller. For more information on firmware revision compatibility, go to

http://www.rockwellautomation.com/support/firmware.html

0xF021

The I/O configuration in the user program is invalid or

does not exist in the Micro800 controller.

Perform the following:

Verify that you have selected the correct Micro800 controller from the
Device Toolbox.

Correct the plug-in I/O module configuration in the user program to match
that of the actual hardware configuration.

Recompile and reload the program.

Put the Micro800 controller into Run mode.

If the error persists, be sure to use Connected Components Workbench
programming software to develop and download the program.

0xF022

The user program in the memory module is incompatible

with the Micro800 controller’s firmware revision.

Perform one of the following:

Upgrade the Micro800 controller’s firmware revision using ControlFlash to
be compatible with the memory module.

Replace the memory module.

Contact your local Rockwell Automation technical support representative
for more information about firmware revisions for your Micro800
controller. For more information on firmware revision compatibility, go to

http://www.rockwellautomation.com/support/firmware.html

0xF023

The controller program has been cleared. This happened

because:

a power down occurred during program download or
transfer from the memory module.

the Flash Integrity Test failed (Micro810 only).

Perform one of the following:

Download the program.

Contact your local Rockwell Automation technical support representative
if the error persists. For contact information, see:

http://support.rockwellautomation.com/MySupport.asp.

0xF030/

0xF031/

0xF032/

0xF033

Power down information in persistent memory may not

be written properly due to a noisy environment or an

internal hardware failure.

If the system variable __SYSVA_USER_DATA_LOST has

been set, the controller will be able to recover the user

program but the user data will be cleared. If not, the

Micro800 controller program will be cleared.

Perform one of the following:

Download the program.

Contact your local Rockwell Automation technical support representative
if the error persists. For contact information, see:

http://support.rockwellautomation.com/MySupport.asp

.

List of Error Codes for Micro800 Controllers

Error Code

Description

Recommended Action