Publication 2098-RM002A-EN-P – October 2001

4-18

Programming Reference

Note: The Set_Attribute_Single service saves parameter values to RAM,

but not to non-volatile storage. To transfer parameter values
from RAM to non-volatile storage, perform one of the following:

• Perform the Save service on the Parameter Object.
• Write the value Execute Command (1) to Parameter 13 - Save

Parameter Values.

Parameter Object,

Instances ID 1- 340
Parameter

Instance

Access

Rule

Parameter

Name

Data

Type

Data

Size

(Bytes)

Units /

Scale

Description

1

Get

DNet Main

Firmware Version

SHORT_S

TRING

1 byte

length

indicator,

1 byte per

character

The version of the main firmware in the

DeviceNet adapter. The format is XX.YY.ZZ,

where:

XX = major revision

YY = minor revision

ZZ = maintenance revision

2

Get

DNet Boot

Firmware Version

SHORT_S

TRING

1 byte

length

indicator,

1 byte per

character

The version of the boot firmware in the adapter.

The format is XX.YY.ZZ, where:

XX = major revision

YY = minor revision

ZZ = maintenance revision

3

Get

Drive Model

SHORT_S

TRING

1 byte

length

indicator,

1 byte per

character

The model number of the drive.

4

Get

DN-SW Node

Address

USINT

1

DeviceNet Node Address (Mac_ID) switch

setting.

5

Get

DN-SW Data

Rate

USINT

1

DeviceNet Data Rate switch setting.

0 = 125 kps

1 = 250 kps

2 = 500 kps

3 = Autobaud

4 = Program

5 = Programmable

6 = Programmable

7 = Programmable

6

Set

DN-NV Node

Address

USINT

1

The programmed nonvolatile DeviceNet Node

Address (Mac_ID).

Range: 0 to 63

Default: 63

Automatically saved in non-volatile storage.

7

Set

DN-NV Data Rate USINT

1

The programmed nonvolatile DeviceNet Data

Rate.

0 = 125 kps (default)

1 = 250 kps

2 = 500 kps

3 = Autobaud

Automatically saved in non-volatile storage.