Rockwell Automation 9303 DRIVE TOOLS32 GETTING STARTED User Manual

Page 51

Advertising
background image

Setting Up DH+ Direct Communications Systems

4-9

Publication 9303-5.13 – March 1998

Setting the
Communication
Information for
DF1(KF2) to DH+

You need to provide DriveTools32 with some information that it needs to
establish a connection between your PC and your drive. To do this, you need to:

1.

Start DriveManager32.

2.

From the Options menu, select Communication Setup. The
Communication Setup dialog box appears.

3.

In the Communications section, select Data Highway Plus (DH+).

4.

In the Communications Type section, select DF1 (KF2) To Data
Highway Plus (DH+)
.

5.

In the Enter mapping Port # to use FOR DF1 drivers field, enter the
KT:0 Port number.

Important: The port number must match the RSLinx KT:0 Port number for the
DF1 device in the Configure Client Applications dialog box.

6.

In the Enter Serial Port Com # field, enter the number of the PC serial
communications port that is being used.

7.

In the Enter Comm Port Baud Rate field, enter the baud rate that your
communications module and port are using. You can choose 2400, 4800,
9600, or 19200 baud.