7-2

Setting Up an Allen-Bradley Ethernet to RIO Block Transfer Pass Thru Communications System

Publication 9303-5.13 – March 1998

Figure 7.1
Allen-Bradley Ethernet Communications System

Important: RIO Block Transfer Pass Thru communications to drives take
approximately 2 seconds per point, and the PLC acting as the gateway must not
use any Block Transfer instructions addressed to the drive in its ladder logic
program.

Important: DriveMonitor32 and DriveBlockEditor32 cannot be used with RIO
Block Transfer Pass Thru communications systems.

Important: For RIO Block Transfer Pass Thru communications to work, the
PLC to which the drive is connected must be in RUN mode. If the PLC is not in
RUN mode, pass thru messages cannot be delivered to the connected drive
product.

Checking Your
Hardware
Installation

Before setting up RSLinx and running DriveTools32, you should check your
hardware installation. You should:

Have an Ethernet card running TCP/IP correctly installed.

Check that all cable connections between the computer and drive are secure.

GD1

Ethernet Connection

ENet RIO BT
Pass Thru

GM1

GK1

1395

SCANport

SCANport

Product

RIO

DH+

Multi-Comm

Adapter

Ethernet

RIO

SCANport

Ethernet

Ethernet

TCP/IP

RIO

SCANport

1336T
(FORCE)

RIO

DH+

PLC Comm

Adapter

Or

Or

Important: For a list of SCANport products,

refer to Appendix A.

PLC-5 (E)