Setting Up a DH+ to RIO Block Transfer Pass Thru Communications System

Publication 9303-5.13 – March 1998

Setting the
Communication
Information

To provide the DriveTools32 with information that it needs to establish a
connection between your PC and your drive, you need to:

1.

Start DriveManager32.

2.

From the Options menu, select Communication Setup. The
Communication Setup dialog box appears.

3.

In the Communications section, select Data Highway Plus (DH+).

4.

In the Communications Type section, select DH+ to PLC RIO
Pass-Thru
.

5.

In the Enter mapping KT(x) Port # to use field, enter the KT Port number.

Important: The KT(x) Port number must match the RSLinx KT:0 Port number
used for the DH+ device in the Configure Client Applications dialog box.

6.

If applicable, select 1336T Two Word Header (used ONLY for 1336T
version 0.10).

7.

Click OK. A window displaying information about RIO Block Transfer
Pass Thru communications appears.

8.

Read the information and click OK.