Rockwell Automation Publication 2080-UM002F-EN-E - December 2013

151

Specifications Appendix A

Outputs

Attribute

2080-LC30-10QWB

2080-LC30-10QVB

Relay Output

Hi-Speed Output
(Outputs 0…1)

Standard Output
(Outputs 2…3)

Output voltage, min

5V DC, 5V AC

10.8V DC

10V DC

Output voltage, max

125V DC, 265V AC

26.4V DC

26.4V DC

Load current, min

10 mA

10 mA

Load current, max

2.0 A

100 mA (high-speed operation)
1.0 A @ 30 °C
0.3 A @ 65 °C (standard operation)

1.0 A @ 30 °C
0.3 A @ 65 °C (standard operation)

Surge current, per point

Refer to Relay Contacts
Ratings on page 151

4.0 A every 1 s @ 30 °C; every 2 s @ 65 °C

(1)

Current, per common, max

5 A

2 A

4 A

Current, per controller, max

1440V A

2 A

4 A

Turn on time/
Turn off time, max

10 ms

2..5

μs

0.1 ms
1.0 ms

(1) Applies for general purpose operation only. Does not apply for high-speed operation.

Relay Contacts Ratings

Maximum Volts

Amperes

Amperes
Continuous

Volt-Amperes

Make

Break

Make

Break

120V AC

15 A

1.5 A

2.0 A

1800V A

180V A

240V AC

7.5 A

0.75 A

24V DC

1.0 A

1.0 A

28V A

125V DC

0.22 A

Environmental Specifications

Attribute

Value

Temperature, operating

IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20…65 °C (-4…149 °F)

Temperature, surrounding air,
max

65 °C (149 °F)

Temperature, non-operating

IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal
Shock):
-40…85 °C (-40…185 °F)

Relative humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…95% non-condensing

Vibration

IEC 60068-2-6 (Test Fc, Operating):
2 g @ 10…500 Hz