Appendix E Troubleshooting
List of Error Codes for Micro800 controllers
Error Code
Description
Recommended Action
0xF000
The controller was unexpectedly reset due to a
noisy environment or an internal hardware
failure.
• A Micro800 controller revision 2.xx and
later attempts to save the program and clear
the user data. If the system variable
_SYSVA_USER_DATA_LOST is set, the
controller is able to recover the user program
but the user data is cleared. If not, the
Micro800 controller program is cleared.
• A Micro800 controller revision 1.xx clears
the program. Note that the system variable
_SYSVA_USER_DATA_LOST is not available
on Micro800 controllers revision 1.xx.
Perform one of the following:
• Download the program through Connected Components Workbench.
• Refer to
Wiring Requirements and Recommendation on page 29
If the fault persists, contact your local Rockwell Automation technical support
representative. For contact information, see:
.
0xF001
The controller program has been cleared. This
happened because:
• a power-down occurred during program
download or data transfer from the memory
module.
• the cable was removed from the controller
during program download.
• the RAM integrity test failed.
Perform one of the following:
• Download the program using Connected Components Workbench.
• Transfer the program using the memory module restore utility.
If the fault persists, contact your local Rockwell Automation technical support
representative. For contact information, see:
.
0xF002
The controller hardware watchdog was activated.
• A Micro800 controller revision 2.xx and
later attempts to save the program and clear
the user data. If the system variable
_SYSVA_USER_DATA_LOST is set, the
controller is able to recover the user program
but the user data is cleared. If not, the
Micro800 controller program is cleared.
• A Micro800 controller revision 1.xx clears
the program. Note that the system variable
_SYSVA_USER_DATA_LOST is not available
on Micro800 controllers revision 1.xx.
Perform the following:
• Establish a connection to the Micro800 controller.
• Download the program using Connected Components Workbench.
If the fault persists, contact your local Rockwell Automation technical support
representative. For contact information, see:
.
0xD00F
A particular hardware type (for example,
embedded I/O) was selected in the user program
configuration, but did not match the actual
hardware base.
Perform one of the following:
• Connect to the hardware that is specified in the user program.
• Reconfigure the program to match the target hardware type.
0xF003
One of the following occurred:
• The memory module hardware faulted.
• The memory module connection faulted.
• The memory module was incompatible with
the Micro800 controller’s firmware revision.
Perform one of the following:
• Remove the memory module and plug it in again.
• Obtain a new memory module.
• Upgrade the Micro800 controller’s firmware revision to be compatible with
the memory module. For more information on firmware revision
compatibility, go to
0xF004
A failure occurred during the memory module
data transfer.
Attempt the data transfer again. If the error persists, replace the memory
module.