Appendix E Troubleshooting

List of Error Codes for Micro800 controllers

Error Code

Description

Recommended Action

0xF000

The controller was unexpectedly reset due to a
noisy environment or an internal hardware
failure.

A Micro800 controller revision 2.xx and

later attempts to save the program and clear
the user data. If the system variable
_SYSVA_USER_DATA_LOST is set, the
controller is able to recover the user program
but the user data is cleared. If not, the
Micro800 controller program is cleared.

A Micro800 controller revision 1.xx clears

the program. Note that the system variable
_SYSVA_USER_DATA_LOST is not available
on Micro800 controllers revision 1.xx.

Perform one of the following:

Download the program through Connected Components Workbench.

Refer to

Wiring Requirements and Recommendation on page 29

If the fault persists, contact your local Rockwell Automation technical support
representative. For contact information, see:

http://support.rockwellautomation.com/MySupport.asp

.

0xF001

The controller program has been cleared. This
happened because:

a power-down occurred during program

download or data transfer from the memory
module.

the cable was removed from the controller

during program download.

the RAM integrity test failed.

Perform one of the following:

Download the program using Connected Components Workbench.

Transfer the program using the memory module restore utility.

If the fault persists, contact your local Rockwell Automation technical support
representative. For contact information, see:

http://support.rockwellautomation.com/MySupport.asp

.

0xF002

The controller hardware watchdog was activated.

A Micro800 controller revision 2.xx and

later attempts to save the program and clear
the user data. If the system variable
_SYSVA_USER_DATA_LOST is set, the
controller is able to recover the user program
but the user data is cleared. If not, the
Micro800 controller program is cleared.

A Micro800 controller revision 1.xx clears

the program. Note that the system variable
_SYSVA_USER_DATA_LOST is not available
on Micro800 controllers revision 1.xx.

Perform the following:

Establish a connection to the Micro800 controller.

Download the program using Connected Components Workbench.

If the fault persists, contact your local Rockwell Automation technical support
representative. For contact information, see:

http://support.rockwellautomation.com/MySupport.asp

.

0xD00F

A particular hardware type (for example,
embedded I/O) was selected in the user program
configuration, but did not match the actual
hardware base.

Perform one of the following:

Connect to the hardware that is specified in the user program.

Reconfigure the program to match the target hardware type.

0xF003

One of the following occurred:

The memory module hardware faulted.

The memory module connection faulted.

The memory module was incompatible with

the Micro800 controller’s firmware revision.

Perform one of the following:

Remove the memory module and plug it in again.

Obtain a new memory module.

Upgrade the Micro800 controller’s firmware revision to be compatible with

the memory module. For more information on firmware revision
compatibility, go to

http://www.rockwellautomation.com/support/firmware.html

0xF004

A failure occurred during the memory module
data transfer.

Attempt the data transfer again. If the error persists, replace the memory
module.