I/O rating

Input 120V AC, 16 mA
Output 2 A, 240V AC,
general use

Input 24V DC, 8.8 mA
Output 2 A, 240V AC,
general use

Input 24V DC, 8.8 mA
Output 24V DC, 1 A per point (Surrounding air temperature
30 °C)
24 V DC, 0.3 A per point (Surrounding air temperature 65 °C)

Insulation stripping
length

7 mm (0.28 in.)

Enclosure type
rating

Meets IP20

Pilot duty rating

C300, R150

Isolation voltage

250V (continuous), Reinforced
Insulation Type, Outputs to Aux
and Network, Inputs to Outputs
Type tested for 60 s @
3250V DC I/O to Aux and
Network, Inputs to Outputs

250V (continuous),
Reinforced Insulation Type,
Outputs to Aux and Network,
Inputs to Outputs
Type tested for 60 s @
720V DC, Inputs to Aux and
Network, 3250V DC Outputs
to Aux and Network, Inputs
to Outputs

50V (continuous), Reinforced Insulation Type, I/O to Aux and
Network, Inputs to Outputs
Type tested for 60 s @ 720V DC, I/O to Aux and Network, Inputs
to Outputs

North American
temp code

T4

(1) Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines, publication

1770-4.1

.

Inputs

Attribute

2080-LC30-48AWB

2080-LC30-48QWB / 2080-LC30-48QVB / 2080-LC30-48QBB

120V AC Input

High-Speed DC Input
(Inputs 0…11)

Standard DC Input
(Inputs 12 and higher)

Number of Inputs

28

12

16

Voltage category

110V AC

24V DC sink/source

Operating voltage

132V, 60Hz AC, max

16.8…26.4V DC

10…26.4V DC

Off-state voltage, max

20V AC

5V DC

Off-state current, max

1.5 mA

1.5 mA

On-state current, min

5 mA @ 79V AC

5.0 mA @ 16.8V DC

1.8 mA @ 10V DC

On-state current, nom

12 mA @ 120V AC

8.8 mA @ 24V DC

8.5 mA @ 24V DC

On-state current, max

16 mA @ 132V AC

12.0 mA @ 30V DC

Nominal impedance

12 k

Ω @ 50 Hz

10 k

Ω @ 60 Hz

3 k

Ω

3.74 k

Ω

IEC input compatibility

Type 3

Inrush current, max

250 mA @ 120V AC

Input frequency, max

63 Hz

AC input filter setting

8 ms for all embedded inputs
(In Connected Components Workbench, go to the Embedded I/O configuration window to reconfigure the filter setting
for each input group)

General Specifications – 2080-LC30-48AWB, 2080-LC30-48QWB, 2080-LC30-48QVB, 2080-LC30-48QBB

Attribute

2080-LC30-48AWB

2080-LC30-48QWB

2080-LC30-48QVB

2080-LC30-48QBB

Advertising