Rockwell Automation 2080-LC50 Micro830 and Micro850 Programmable Controllers User Manual User Manual

Page 174

Advertising
background image

158

Rockwell Automation Publication 2080-UM002F-EN-E - December 2013

Appendix A Specifications

Nominal impedance

3 k

Ω

3.74 k

Ω

IEC input compatibility

Type 3

AC input filter setting

8 ms for all embedded inputs
(In Connected Components Workbench, go to the Embedded I/O
configuration window to re-configure the filter setting for each input
group)

Isolated AC Inputs (2080-LC30-24QWB, 2080-LC30-24QVB, 2080-LC30-24QBB)
(Inputs 0…7)

Attribute

Value

On-state voltage, nom

12/24V AC @ 50/60 Hz

Off-state voltage, min

4V AC @ 50/60Hz

Operating frequency, nom

50/60 Hz

Inputs

Attribute

High-Speed DC Input
(Inputs 0…7)

Standard DC Input
(Inputs 8 and higher)

Outputs

Attribute

2080-LC30-24QWB

2080-LC30-24QVB / 2080-LC30-24QBB

Relay Output

Hi-Speed Output
(Outputs 0…1)

Standard Output
(Outputs 2 and higher)

Number of outputs

10

2

8

Output voltage, min

5V DC, 5V AC

10.8V DC

10V DC

Output voltage, max

125V DC, 265V AC

26.4V DC

26.4V DC

Load current, min

10 mA

Load current, max

2.0 A

100 mA (high-speed operation)
1.0 A @ 30 °C
0.3 A @ 65 °C (standard operation)

1.0 A @ 30 °C
0.3 A @ 65 °C (standard operation)

Surge current, per point

Refer to Relay Contacts Ratings
on page 158

4.0 A every 1 s @ 30 °C; every 2 s @ 65 °C

(1)

Current, per common, max

5 A

Turn on time/
Turn off time, max

10 ms

2.5

μs

0.1 ms
1 ms

(1) Applies for general purpose operation only. Does not apply for high-speed operation.

Relay Contacts Ratings

Maximum Volts

Amperes

Amperes
Continuous

Volt-Amperes

Make

Break

Make

Break

120V AC

15 A

1.5 A

2.0 A

1800V A

180V A

240V AC

7.5 A

0.75 A

24V DC

1.0 A

1.0 A

28V A

125V DC

0.22 A