Rockwell Automation Publication 2080-UM002F-EN-E - December 2013

Appendix C Quickstarts

1.

On the Initial Value field for the MyCommand variable, type 1.
See

HSC Commands (HScCmd) on page 135

for more information on

the description for each value.

2.

Assign values to the MyAppData variables. Expand the list of MyAppData
sub-variables clicking the + sign. Set the values of the different sub-
variables as shown in the following screenshot.

MyAppData.PlsEnable

allows the user to either enable or disable the PLS

settings. It should be set to FALSE (disabled) if the MyAppData variable is
to be used.

MyAppData.HscID

allows the user to specify which embedded inputs

will be used depending on the mode and the type of application. See the
table

HSC Inputs and Wiring Mapping on page 113

to know the different

IDs that can be used as well as the embedded inputs and its characteristics.

If ID 0 is used, ID 1 cannot be used on the same controller since the inputs
are being used by the Reset and Hold.

MyAppData.HscMode

allows the user to specify the type of operation in

which the HSC will use to count. See

HSC Mode (HSCAPP.HSCMode)

IMPORTANT

MyAppData variable has sub-variables which determine the settings of
the counter. It is crucial to know each one in order to determine how the
counter will perform. A quick summary is provided below but you can
also see

HSC APP Data Structure on page 117

for detailed information.