Appendix E Troubleshooting
Normal Operation
The POWER and RUN indicators are on. If a force condition is active, the
FORCE indicator turns on and remains on until all forces are removed.
Error Conditions
If an error exists within the controller, the controller indicators operate as
described in the following table.
4
Fault status
Off
No fault detected.
Red
Controller hard fault.
Flashing red
Application fault detected.
5
Force status
Off
No force conditions are active.
Amber
Force conditions are active.
6
Serial
communications
status
Off
No traffic for RS-232/RS-485.
Green
Traffic through RS-232/RS-485.
7
Output status
Off
Output is not energized.
On
Output is energized (logic status).
8
Module status
Steady Off
No power.
Flashing Green
Standby.
Steady Green
Device operational.
Flashing Red
Minor fault
(minor and major recoverable faults).
Steady Red
Major Fault (non-recoverable fault).
Flashing Green
and Red
Self-test.
9
Network status
Steady Off
Not powered, no IP address.
The device is powered off, or is powered on but
with no IP address.
Flashing Green
No connections.
An IP address is configured, but no Ethernet
application is connected.
Steady Green
Connected.
At least one EtherNet/IP session is established.
Flashing Red
Connection timeout (not implemented).
Steady Red
Duplicate IP.
The device has detected that its IP address is being
used by another device in the network. This status
is applicable only if the device's duplicate IP
address detection (ACD) feature is enabled.
Flashing Green
and Red
Self-test.
The device is performing power-on self-test
(POST). During POST, the network status indicator
alternates flashing green and red.
Status Indicator Description
Description
State
Indicates