Rockwell Automation 2080-LC50 Micro830 and Micro850 Programmable Controllers User Manual User Manual
Page 247

Rockwell Automation Publication 2080-UM002F-EN-E - December 2013
231
Troubleshooting Appendix E
0xF005
The user program failed an integrity check while
the Micro800 controller was in Run mode.
Perform one of the following:
• Cycle power on your Micro800 controller. Then, download your program
using Connected Components Workbench and start up your system.
Wire Your Controller on page 29
0xF006
The user program is incompatible with the
Micro800 controller’s firmware revision.
Perform one of the following:
• Upgrade the Micro800 controller’s firmware revision using ControlFlash.
• Contact your local Rockwell Automation technical support representative for
more information about firmware revisions for your Micro800 controller. For
more information on firmware revision compatibility, go to
0xF010
The user program contains a function/function
block that is not supported by the Micro800
controller.
Perform the following:
• Modify the program so that all functions/function blocks are supported by
the Micro800 controller.
• Build and download the program using Connected Components Workbench.
• Put the Micro800 controller into Run mode.
0xF014
A memory module memory error occurred.
Reprogram the memory module. If the error persists, replace the memory
module.
0xF015
An unexpected software error occurred.
Perform the following:
1. Cycle power on your Micro800 controller.
2. Build and download your program using Connected Components Workbench,
and then reinitialize any necessary data.
3. Start up your system.
Wire Your Controller on page 29
0xF016
An unexpected hardware error occurred.
Perform the following:
1. Cycle power on your Micro800 controller.
2. Build and download your program using Connected Components Workbench,
and then reinitialize any necessary data.
3. Start up your system.
Wire Your Controller on page 29
OxF019
An unexpected software error occurred due to
memory or other controller resource issue.
Perform the following:
1. Cycle power on your Micro800 controller.
2. Build and download your program using Connected Components Workbench,
and then reinitialize any necessary data.
3. Start up your system.
0xF020
The base hardware faulted or is incompatible
with the Micro800 controller’s firmware revision.
Perform one of the following:
• Upgrade the Micro800 controller’s firmware revision using ControlFlash.
• Replace the Micro800 controller.
• Contact your local Rockwell Automation technical support representative for
more information about firmware revisions for your Micro800 controller. For
more information on firmware revision compatibility, go to
List of Error Codes for Micro800 controllers
Error Code
Description
Recommended Action