Appendix E Troubleshooting

0xF021

The I/O configuration in the user program is
invalid or does not exist in the Micro800
controller.

Perform the following:

Verify that you have selected the correct Micro800 controller from the Device

Toolbox.

Correct the plug-in I/O module configuration in the user program to match

that of the actual hardware configuration.

Recompile and reload the program.

Put the Micro800 controller into Run mode.

If the error persists, be sure to use Connected Components Workbench

programming software to develop and download the program.

0xF022

The user program in the memory module is
incompatible with the Micro800 controller’s
firmware revision.

Perform one of the following:

Upgrade the Micro800 controller’s firmware revision using ControlFlash to be

compatible with the memory module.

Replace the memory module.

Contact your local Rockwell Automation technical support representative for

more information about firmware revisions for your Micro800 controller. For
more information on firmware revision compatibility, go to

http://www.rockwellautomation.com/support/firmware.html

0xF023

The controller program has been cleared. This
happened because:

a power down occurred during program

download or transfer from the memory
module.

the Flash Integrity Test failed (Micro810 only).

Download or transfer the program.

0xF050

The embedded I/O configuration in the user
program is invalid.

Perform the following:

Correct the embedded I/O configuration in the user program to match that of

the actual hardware configuration.

Build and download the program using Connected Components Workbench.

Put the Micro800 controller into Run mode.

If the error persists, be sure to use Connected Components Workbench

programming software to develop and download the program.

0xF100

There is general configuration error detected in
the motion configuration downloaded from the
Connected Components Workbench software,
such as number of axis, or motion execution
interval being configured out of range.

Perform the following:

Correct the axes configuration in the user program.

If fault is consistent, upgrade to the latest software revision of Connected

Components Workbench.

See

Motion Axis Configuration in Connected Components Workbench on

page 89

.

0xF110

There is motion resource missing, such as
Motion_DIAG variable not defined.

Perform the following:

Correct the axes configuration in the user program.

If fault is consistent, upgrade to the latest Connected Components

Workbench software revision.

See

Motion Axis Configuration in Connected Components Workbench on

page 89

.

List of Error Codes for Micro800 controllers

Error Code

Description

Recommended Action