Appendix E Troubleshooting

0xF29z
(z indicates the
slot number of the
expansion I/O. If
z=0, then the slot
number cannot be
identified.)

A module fault is detected on your expansion I/O
module.

Perform the following:

Cycle power the Micro800 controller, or

Replace the slot number z module.

If the error persists, contact your local Rockwell Automation technical support
representative. For contact information, see

http://support.rockwellautomation.com/MySupport.asp

.

0xF2Az
(z indicates the
slot number of the
expansion I/O. If
z=0, then the slot
number cannot be
identified.)

Expansion I/O power failure

Perform the following:

Cycle power the Micro800 controller, or

Replace the slot number z module.

If the error persists, contact your local Rockwell Automation technical support
representative. For contact information, see

http://support.rockwellautomation.com/MySupport.asp

.

0xF2Bz
(z indicates the
slot number of the
expansion I/O. If
z=0, then the slot
number cannot be
identified.)

Expansion I/O configuration fault.

Perform the following:

Correct the expansion IO module configuration in the user program to match

that of the actual hardware configuration.

Check the expansion I/O module operation and condition.

Cycle power to the Micro800 controller.

Replace the expansion I/O module.

For the following four error codes, z is the slot number of the plug-in module. If z = 0, then the slot number cannot be identified

0xF0Az

The plug-in I/O module experienced an error
during operation.

Perform one of the following:

Check the condition and operation of the plug-in I/O module.

Cycle power to the Micro800 controller.

If the error persists, see the Micro800 Plug-In Modules, publication

2080-

UM004

.

0xF0Bz

The plug-in I/O module configuration does not
match the actual I/O configuration detected.

Perform one of the following:

Correct the plug-in I/O module configuration in the user program to match

that of the actual hardware configuration.

Check the condition and operation of the plug-in I/O module.

Cycle power to the Micro800 controller.

Replace the plug-in I/O module.

If the error persists, see the Micro800 Plug-in Modules, publication

2080-UM004

.

0xF0Dz

When power was applied to the plug-in I/O
module or the plug-in I/O module was removed, a
hardware error occurred.

Perform the following:

Correct the plug-in I/O module configuration in the user program.

Build and download the program using Connected Components Workbench.

Put the Micro800 controller into Run mode.

0xF0Ez

The plug-in I/O module configuration does not
match the actual I/O configuration detected.

Perform the following:

Correct the plug-in I/O module configuration in the user program.

Build and download the program using Connected Components Workbench.

Put the Micro800 controller into Run mode.

List of Error Codes for Micro800 controllers

Error Code

Description

Recommended Action