2-2 Understanding Configurable FLEX Ex Analog Module Features

You must use the I/O configuration portion of your PLC programming
software to select and configure these features. This manual assumes
familiarity with the programming software. A brief description of each
module feature is provided here. For more information on your
programming software, see the software user manual.

Selecting a 1797-IE8 or
-IE8NF FLEX Ex Analog
Input Module’s Operating
Features

All features of the 1797-IE8 and -IE8NF analog input modules are
independently configurable in two four-channel groups (channel 0-3 &
channel 4-7).

Fault Mode

Your input modules are capable of indicating various fault conditions,
depending on the input signal value. Use the Fault Mode feature to enable or
disable two alarms:

• Remote Fault alarm
• Local Fault alarm

Use your programming software to set the Fault Mode bit to 0 to disable these
alarms. Set the bit to 1 to enable them.

For more information on Remote and Local Fault alarms, see page 1-5.

IMPORTANT

The default selection value for all parameters is 0.

IMPORTANT

Fault Mode will only enable or disable the Remote and
Local Fault alarms. It does not affect the Underrange and
Overrange alarms. They are always active.