Troubleshooting the FLEX Ex
Analog I/O Modules

What this Chapter Contains

Read this chapter to troubleshoot your I/O module.

Status Indicators

1797-IE8 and -IE8NF Modules

The 1797-IE8 and -IE8NF modules have one power indicator that is on when
power is applied to the module and one status indicator for each input.

For information on:

See page:

Status Indicators

7-1

Repair

7-2

Chapter Summary

7-2

Indicator

Color

State

Meaning

Status

Red

On

At power up – Channel 0 indicator lights at powerup until
all internal diagnostics are checked. After successful
powerup, the indicator goes off if no fault is present.
After successful powerup – Indicates a critical fault
(diagnostic failure, etc.)

Blinking (when
faults are
enabled, and bit
set)

Indicates a noncritical channel fault

Power

Off

Module not powered

Green

On

Module receiving power

Ex

PWR

1797-IE8

8 CHANNEL ANALOG INPUT

IN1

IN0

IN2

IN3

IN4

IN5

IN6

IN7

3

40070

A

B

C

A = Status indicators
B = Insertable labels for writing individual input designations
C = Power indicator