5-2 Calibrating Your Module
Use one of the following general methods to calibrate your module:
• Use intrinsically safe equipment to calibrate the module.
• Use factory trained personnel under controlled conditions to calibrate
the modules with non-intrinsically safe equipment to maintain your 
module’s intrinsic safety certification.
Tools and Equipment
To calibrate your analog I/O modules, you will need the following tools and 
equipment:
Using Calibration Module 
Command Words
Module calibration is supported by Module Command words. See your 
module data tables in Chapter 3 to determine which words are the Module 
Command words. They are always the last read word and last write word. The 
Module Command word is broken into two parts the upper byte is the 
command and the lower byte is the data.
A CIO is used to structure a calibration command and submit it to the 
network. This includes the command and any data. 
ATTENTION
With the second method, extreme care must be exercised 
by the calibration personnel to avoid compromising the 
intrinsically safe characteristics or your modules. This 
method may never be used in a hazardous environment.
Table 5.1 Tools for Calibration
Tool or Equipment:
Description:
Precision Current 
Source
0-22mA, 0.01µA resolution
Used for input modules
Precision Current Meter 0-22mA, 0.01µA resolution
Used for output modules
Industrial Terminal and 
Interconnect Cable
Programming terminal for A-B family processors
Table 5.2 MODULE Command Word
R/W
Bit
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Write
cmd 
flag
MODULE calibration command
MODULE calibration command data