5-2 Calibrating Your Module

Use one of the following general methods to calibrate your module:

• Use intrinsically safe equipment to calibrate the module.

• Use factory trained personnel under controlled conditions to calibrate

the modules with non-intrinsically safe equipment to maintain your
module’s intrinsic safety certification.

Tools and Equipment

To calibrate your analog I/O modules, you will need the following tools and
equipment:

Using Calibration Module
Command Words

Module calibration is supported by Module Command words. See your
module data tables in Chapter 3 to determine which words are the Module
Command words. They are always the last read word and last write word. The
Module Command word is broken into two parts the upper byte is the
command and the lower byte is the data.

A CIO is used to structure a calibration command and submit it to the
network. This includes the command and any data.

ATTENTION

With the second method, extreme care must be exercised
by the calibration personnel to avoid compromising the
intrinsically safe characteristics or your modules. This
method may never be used in a hazardous environment.

Table 5.1 Tools for Calibration

Tool or Equipment:

Description:

Precision Current
Source

0-22mA, 0.01µA resolution

Used for input modules

Precision Current Meter 0-22mA, 0.01µA resolution

Used for output modules

Industrial Terminal and
Interconnect Cable

Programming terminal for A-B family processors

Table 5.2 MODULE Command Word

R/W

Bit

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Write

cmd
flag

MODULE calibration command

MODULE calibration command data