Rockwell Automation 1797-OE8 FLEX Ex Analog Modules User Manual User Manual

Page 83

Advertising
background image

Publication 1797-6.5.1 - May 2005

Specifications A-3

1797-IE8 and -IE8NF CE, CENELEC I/O Entity Parameters

Measurement input (sig to -) for ch 0 to ch 7 (terminals: 1-2; 5-6; 9-10;
13-14; 18-19; 22-23; 26-27; 30-31)

Source output (+ to sig) for ch 0 to ch 7 (terminals: 0-1; 4-5; 8-9; 12-13; 17-18;
21-22; 25-26; 29-30)

Source output plus measurement input (+ to -) for ch 0 to ch 7 (terminals: 0-2;
4-6; 8-10; 12-14; 17-19; 21-23; 25-27; 29-31)

Protection

Group

Allowed
Capacitance

Allowed
Inductance

U

o

= 5V

I

o

= 1mA

P

o

= 1.3mW

EEx ia

IIB

1000µF

1H

U

i

= 28V

I

i

= 93mA

C

i

and L

i

negligible

IIC

100µF

1H

Protection

Group

Allowed
Capacitance

Allowed
Inductance

U

o

= 23.7V

I

o

= 92.5mA

P

o

= 548mW

EEx ia

IIB

560nF

10mH

IIC

66nF

2.5mH

If concentrated
capacitance
and/or
inductance are
available, use the
following values.

EEx ia

IIB

320nF

10mH

IIC

60nF

2mH

Protection

Group

Allowed
Capacitance

Allowed
Inductance

U

o

= 23.7V

I

o

= 93.5mA

P

o

= 555mW

EEx ia

IIB

560nF

10mH

IIC

66nF

2.5mH

If concentrated
capacitance
and/or
inductance are
available, use the
following values.

EEx ia

IIB

320nF

10mH

IIC

60nF

2mH

Advertising