1797-ie8 and -ie8nf fm i/o entity parameters – Rockwell Automation 1797-OE8 FLEX Ex Analog Modules User Manual User Manual

Page 87

Advertising
background image

Publication 1797-6.5.1 - May 2005

Specifications A-7

1797-IE8 and -IE8NF FM I/O Entity Parameters

If this product has the FM mark, it has been designed, evaluated, tested, and
certified to meet the following standards:

• FM C1. No.3600:1998, Electrical Equipment for Use in Hazardous

(Classified) Locations General Requirements

• FM C1. No.3610:1999, Intrinsically Safe Apparatus and Associated

Apparatus for Use in Class I, II, III Division 1 Hazardous (Classified)
Locations

• FM C1. No.3615:1989, Explosionproof Electrical Equipment General

Requirements

• FM C1. No.3810:1989, 1995, Electrical and Electronic Test, Measuring

and Process Control Equipment

• ANSI/NEMA 250, 1991, Enclosures for Electrical Equipment

Wiring Methods

• Wiring method 1 - Each channel is wired separately.
• Wiring method 2 - Multiple channels in one cable, providing each

channel is separated in accordance with the National Electric Code
(NEC).

Table 1

Wiring

Method

Channel

Terminals

V

oc

(V)

I

sc

(mA)

V

t

(V)

I

t

(mA)

Groups

C

a

(

µF)

L

a

(mH)

1 and 2

Any one

channel
e.g. ch0

0(+), 1(sig)

23.7

92.5

-

-

A, B

0.15

4.0

C, E

0.45

12.0

D, F, G

1.20

32.0

1(sig), 2(-)

5

1.0

-

-

A, B

100

1000

C, E

300

1000

D, F, G

800

1000

0(+), 1(sig), 2(-)

-

-

23.7

93.5

A, B

0.15

4.0

C, E

0.45

12.0

D, F, G

1.20

32.0