Publication 1797-6.5.1 - May 2005

6-4 Applying FLEX Ex Analog I/O Modules

1797-IE8 and -IE8NF Functional and IS Parameters

The figure below provides data, on the Flex Ex analog input modules, which
can be matched to this transmitter.

Loop Functionality Verification

The functional characteristics will be checked first. The figure below shows the
general situation which must be analyzed for proper loop function.

On the left are the module components of the voltage source to run the loop
and its internal source resistance. In the center is the cable. It represents a loss
with regard to its resistance. Cable resistance is a function of cable length. On
the right is the transmitter, which has a minimum voltage it must see to
function properly.

I

Analog Input

V>17V at I=0mA

V>15.5 at I=20mA

V>15V at I=22mA

0-22mA Measurement Range

EEx ia/ib IIB/IIC T4

Uo<23.7V

Io<92.5mA

Flexbus

41662

IIB

Ca=560nF

La=10mH

IIC

Ca=66nF

La=2.5mH

P

+

-V

sig

+V

4-20mA

Xmit

91

17V

22

Bus

uC

Ci<10pF/m

Li<0.5uH/m

R<0.1

Ω/m

41664

IIB

Ca=560nF

La=10mH

transmitter

minimum

voltage=10.5V

+

cable resistance loss

+

module source voltage=17V

module source resistance=91

+

sig

22

module sense

resistance=22

91

17V