2-12 Understanding Configurable FLEX Ex Analog Module Features

Fault Alarm

Fault Alarm selects whether the channel pair fault detection is enabled or
disabled. There is a 100Hz (10ms) filter for wire off/lead break detection.

Use your programming software to set the Fault Alarm. Set the feature bit
to 0 to disable the alarm. Set the bit to 1 to enable wire off/lead break
fault detection.

10

0-20mA

0-20mA

not assigned

11

D/A count
as 0-20mA

0.28% of
0-20mA

0-22mA

0-8000
(0-22mA)

363

min=0mA
max=22mA
hold
last=hold
50%=11mA

12

4-20mA

not assigned

13

% as
4-20mA

0.16% of
4-20mA

3-21mA

-625 - +10625
(2’s complement)
(-6.25% -
+106.25%)

625

min=3mA
max=21mA
hold
last=hold
50%=12mA

14

% as
4-20mA

0.16% of
4-20mA

2-22mA

-1250 - +11250
(2’s complement)
(-12.50% -
+112.50%)

625

min=2mA
max=22mA
hold
last=hold
50%=12mA

15

4-20mA

4-20mA

not assigned

Table 2.4 1797-OE8 Data Formats

Data
Format

Format

Resolution Full

Output
Range

Module Data Processing

Data Table Value
(Interpretation)

Count
per mA

Analog Fault
State

output = 22

datatable

(

8,000

)

output = 16

datatable

(

10,000

)

+ 4

output = 16

datatable

(

10,000

)

+ 4