Important, 8v; i, 5v; i – Rockwell Automation 1797-OE8 FLEX Ex Analog Modules User Manual User Manual
Page 85
 
Publication 1797-6.5.1 - May 2005
Specifications A-5
IMPORTANT
A terminal base may or may not have an I/O module installed.
1797- IE8
Allen-Bradley
B
-
A
7
PWR
0
1
2
3
4
5
6
3
8 CHANNEL ANALOG INPUT
FLEX Ex Analog Input 
I/O Module
LEDs
Female Bus 
Connection
Field Wiring 
Terminals
Terminal Base
Terminal Base 
Key
Male Bus 
Connection
Key Position for 
Terminal Base 
Insertion
42055
Hazardous (Classified) Location
Class I, Zones 0, 1, & 2 Groups IIC, IIB, IIA
Class I, Div. 1 & 2 Groups A, B, C, D
Class II, Div. 1 & 2 Groups E, F, G
Class III, Div. 1 & 2
Hazardous (Classified) Location
Class I, Zones 1 & 2 Groups IIC, IIB, IIA
Class I, Div. 1 & 2 Groups A, B, C, D
To any intrinsically safe 
device or associated 
apparatus with Entity 
Concept parameters of 
V
oc
< 5.8V; I
sc
< 400mA.
To any intrinsically safe 
device or associated 
apparatus with Entity 
Concept parameters of 
V
oc
< 9.5V; I
sc
< 1A.
To any IS device with Entity 
Concept parameters of 
(V
max
, I
max
, C
i
, L
i
) appropriate
for connection to associated 
apparatus with Entity Concept 
parameters listed in Table 2.
1797-IE8
or
1797-IE8NF
16
Shield Connection Only
50
51
35
34
V
max
=5.8V
I
max
=400mA
C
i
=1350nF
L
i
=negligible
V
max
=9.5V
I
max
=1A
C
i
=negligible
L
i
=negligible
Male Bus 
Connector
33
40
41
42
43
44
45
0 (+)
Female Bus 
Connector
Any Simple Apparatus or I.S. 
device with Entity Concept 
parameters (V
max
, I
max
, C
i
, L
i
)
appropriate for connection to 
associated apparatus with Entity 
Concept parameters listed in Table 
1.
1 (sig)
ch0
ch1
ch2
ch3
ch4
ch5
ch6
ch7
2 (-)
4 (+)
5 (sig)
6 (-)
8 (+)
9 (sig)
10 (-)
12 (+)
13 (sig)
14 (-)
17 (+)
18 (sig)
19 (-)
21 (+)
22 (sig)
23 (-)
25 (+)
26 (sig)
27 (-)
29 (+)
30 (sig)
31 (-)
42056