Publication 1797-6.5.1 - May 2005

Input, Output, and Configuration Files for the Analog I/O Modules on the ControlNet Network 4-5

Adapter Status Word

The status word consists of:

• I/O module fault bits – 1 status bit for each slot

Additionally, in the case of a PLC-5 controller, it adds:

• node address changed – 1 bit (created by PLC-5 controller)

• I/O status – 1 bit (created by PLC-5 controller)

The following FLEX Ex adapter status word for a PLC-5 controller results.

As an example, in a PLC-5 system, the adapter status word bit descriptions are
shown in the following table.

41629

Bit:

15

9

10 through 15

8

7

6

5

4

3

2

1

0

I/O Module Fault Bits

I/O Status Bit

Node Address Changed Bit

Created by PLC-5 controller

Table 4.1 Adapter Status Word Bit Descriptions

Bit Description:

Bit:

Explanation:

I/O Module Fault

0

This bit is set (1) when an error is detected in slot position 0.

1

This bit is set (1) when an error is detected in slot position 1.

2

This bit is set (1) when an error is detected in slot position 2.

3

This bit is set (1) when an error is detected in slot position 3.

4

This bit is set (1) when an error is detected in slot position 4.

5

This bit is set (1) when an error is detected in slot position 5.

6

This bit is set (1) when an error is detected in slot position 6.

7

This bit is set (1) when an error is detected in slot position 7.

Node Address Changed
(Created by PLC-5
controller.)

8

This bit is set (1) when the node address switch setting has
been changed since power-up.

I/O State (Created by
PLC-5 controller.)

9

Bit = 0 -idle
bit = 1 - run

10 though 15

Not used – set to 0