Publication 1797-6.5.1 - May 2005

A-12 Specifications

1797-OE8 UL, C-UL I/O Entity Parameters

If this product has the UL/C-UL mark, it has been designed, evaluated, tested,
and certified to meet the following standards:

• UL 913, 1988, Intrinsically Safe Apparatus and Associated Apparatus

for Use in Class I, II, and III Division 1, Hazardous (Classified)
Locations

• UL 1203, Explosion-Proof and Dust-Ignition-Proof Electrical

Equipment for Use in Hazardous (Classified) Locations

• UL 2279, Electrical Equipment for Use in Class I, Zone 0, 1, and 2

Hazardous (Classified) Locations

• UL 508, Industrial Control Equipment
• CSA C22.2 No. 157-92, Intrinsically Safe and Non-Incendive

Equipment for Use in Hazardous Locations

• CSA C22.2 No. 30-M1986, Explosion-Proof Enclosures for Use in

Class I Hazardous Locations

• CSA-E79-0-95, Electrical Apparatus for Explosive Gas Atmospheres,

Part 0: General Requirements

• CSA-E79-11-95, Electrical Apparatus for Explosive Gas Atmospheres,

Part 11: Intrinsic Safety “i”

• CSA C22.2 No. 14-95, Industrial Control Equipment

Wiring Methods

• Wiring method 1 - Each channel is wired separately.
• Wiring method 2 - Multiple channels in one cable, providing each

channel is separated in accordance with the National Electric Code
(NEC) or Canadian Electric Code (CEC).

Table 1

Wiring

Method

Channel Terminal

s

V

oc

(V)

I

sc

(mA)

V

t

(V)

I

t

(mA)

Groups

C

a

(

µF)

L

a

(mH)

1 and 2

Any one

channel
e.g. ch0

0(+), 1(-)

21.0

100.0

-

-

A, B, IIC

0.08

2.0

C, E, IIB

0.24

8.0

D, F, G, IIA

0.64

16.0