5-10 Calibrating Your Module

The following table shows the calibration MODULE command definitions.

Chapter Summary

In this chapter, you learned how to calibrate your FLEX Ex analog I/O
modules. Move to Chapter 6 to see how to apply FLEX Ex analog I/O
modules.

Table 5.9 Calibration MODULE Command Definitions

MODULE Calibration Command

MODULE Calibration Command Data

Command

Meaning

Data (up nibble)

Data (low nibble)

Meaning

channel

command

0

Commands Idle

x

x

command method is idle

1

No Operation

x

x

no operation is required

4

General Calibration by Channel

0-7

0

zero min scale and max scale coefficients

0-7

1-15

not used

8-15

0-15

not used

5

Min Scale Calibration by

Channel

0-7

0

output = 1mA

0-7

1

accept value in channel data word as min

scale calibration

0-7

2-15

not used

8-15

0-15

not used

6

Max Scale Calibration by

Channel

0-7

0

output = 21mA

0-7

1

accept value in channel data word as max

scale calibration

0-7

2-15

not used

8-15

0-15

not used

36

Calibration all Channels

General Calibration all Channels

0

0

zero min scale and max scale coefficients

0

1-15

not used

Min Scale Calibration all

Channels

1

0

output = 1mA

1

1

accept values in channel data words as min

scale calibration

1

2-15

not used

Max Scale Calibration all

Channels

2

0

output = 21mA

2

1

accept values in channel data words as

max scale calibration

2

2-15

not used

3-15

0-15

not used