Intrinsic safety entity verification -6, Intrinsic safety entity verification – Rockwell Automation 1797-OE8 FLEX Ex Analog Modules User Manual User Manual

Page 72

Advertising
background image

Publication 1797-6.5.1 - May 2005

6-6 Applying FLEX Ex Analog I/O Modules

Intrinsic Safety Entity Verification

Next we must determine if the pressure to current analog transmitter and the
Flex Ex analog input module are compatible from an IS perspective. We will
make this determination for a IIC gas application.

The figure below shows an extraction of pertinent information from the
figures on pages 6-3.

In the figure above, three key items are shown, the field device the
interconnecting cabling and the Flex Ex module (in this example, a 1797-IE8).
The entity verification is done for the gas group IIC. As the table shows, the
module’s entity parameters are compared to the combination of the transmitter
and the wiring entity parameters.

The module’s entity parameters are shown in the Module column on the left.
They must be compared with the parameters shown in the Total Loop column,
in the manner shown. The values in the Total Loop column are determined in
the following manner:

• Total Loop U

i

= Transmitter U

i

• Total Loop I

i

= Transmitter I

i

• Total Loop C

i

= (Transmitter C

i

+ Cabling C

i

per length) X (cable

length)

• Total Loop L

i

= (Transmitter L

i

+ Cabling L

i

per length) X (cable

length)

As long as the Module and Total Loop entity parameters satisfy the inequalities
shown the loop is acceptable for use in the hazardous environment.

=
=
=
=

=
=
=
=

Ci<10pF/m

Li<0.5uH/m

R<0.1

Ω/m

41665

P/I transmitter

EEx ia IIC T4

Ui=30V

Ii=165mA

Ci=22.5nF

Li=730uH

+

cable length = 10m

+

sig

22

1797-IE8 Analog Input

EEx ia/ib IIB/IIC T4

Uo<23.7V

lo<92.5mA

91

17V

IIB

Ca=560nF

La=10mH

IIC

Ca=66nF

La=2.5mH

Module

Uo

Io

Ca

La

Module

Uo<23.7V

Io<92.5mA

Ca=66nF

La=2.5mH

< or =
< or =
> or =
> or =

< or =
< or =
> or =
> or =

Total Loop

Ui

Ii

Ci

Li

Module

Ui=30V

Ii=165

Ci=22.6nF

Li=735uH

Distance

(length
(length

Distance

(10m
(10m

Cable

Ci per length)

La per length)

Cable

Ci=10pF/m)

La=0.5uH/m)

Total Loop

Ui

Ii

Ci

Li

Module

Ui=30V

Ii=165

Ci=22.5nF

Li=735uH

+

+
+

*
*

*
*

Advertising