Rockwell Automation 1797-OE8 FLEX Ex Analog Modules User Manual User Manual

Page 82

Advertising
background image

Publication 1797-6.5.1 - May 2005

A-2 Specifications

Power Dissipation

5.2W

Thermal Dissipation

17.75 BTU/hr

Module Location

Cat. No. 1797-TB3 or -TB3S

Conductor Wire Size

12 gauge (4mm

2

) stranded maximum

3/64in (1.2mm) insulation maximum

Dimensions

46mm x 94mm x 75mm
(1.8in x 3.7in x 2.95in)

Weight

200g (approximately)

Keyswitch Position

3

Environmental Conditions

Operational Temperature
Storage Temperature
Relative Humidity
Shock

Operating
Nonoperating
Vibration

-20 to +70

o

C (-4 to +158

o

F)

-40 to +85

o

C (-40 to +185

o

F)

5 to 95% noncondensing
Tested to 15g peak acceleration, 11(+1)ms pulse width
Tested to 15g peak acceleration, 11(+1)ms pulse width
Tested 2g @ 10-500Hz per IEC68-2-6

Agency Certification

CENELEC

UL, C-UL

FM

II (1) 2G EEx ia/ib IIB/IIC T4
II (1D) (2D)
Class I Division 1 & 2 Groups A-D T4
Class I Zone 1 & 2 AEx ib/[ia] IIC T4
Class I Division 1 Groups A-D T4
Class I Zone 1 AEx ib/[ia] IIC T4

Certificates

CENELEC

DMT 98 ATEX E 020 X

UL, C-UL

UL Certificate Number 99.19699

FM

FM Certificate Number 3009806

Class I Division 1 Hazardous

C

US

FM

Advertising