Publication 1797-6.5.1 - May 2005

How to Install Your FLEX Ex Analog Modules 3-13

Connections for the 1797-OE8 Module

1. Connect the individual output wiring to (+) terminals (0, 4, 8, 12) on the

0-15 row (A) and on the 16-33 row (B) (terminals 17, 21, 25, 29) as
indicated in the table below.

2. Connect the associated output to the corresponding (-) terminal (1, 5, 9,

13) on the 0-15 row (A), and on the 16-33 row (B) (terminals 18, 22, 26,
30) for each input as indicated in the following table.

3. Connect +V dc power to terminal 34 on the 34-51 row (C).

4. Connect -V to terminal 35 on the 34-51 row (C).

5. If continuing power to the next terminal base unit, connect a jumper

from terminal 50 (+V) on this base unit to terminal 34 on the next base
unit.

6. If continuing common to the next terminal base unit, connect a jumper

from terminal 51 (-V) on this base unit to terminal 35 on the next base
unit.

flexbus

Bus

uC

+V

-V

+

-

power
supply

4-20mA
actuator

4-20mA
valve

41441

41440

Row A

Row B

Row C

ch0

ch1

ch2

ch3

+V

+V

-V

-V

0

1

2

3

4

5

6

7

8

9

10 11 12 13 14

15

16

17 18 19

20 21 22 23 24 25 26 27 28 29 30 31

32 33

34

35 36 37

38 39 40 41 42 43 44 45 46 47 48 49

50 51

+

+

+

+

-

-

-

-

ch4

ch5

ch6

ch7

+ -

+ -

+ -

+ -

No connections allowed to terminals 2, 3, 6, 7, 10, 11, 14, 15, 19, 20, 23,
24, 27, 28, 31, 32, 36, 37, 38, 39, 46, 47, 48, 49

1797-OE8 Module