Rockwell Automation 1797-OE8 FLEX Ex Analog Modules User Manual User Manual

Page 27

Advertising
background image

Publication 1797-6.5.1 - May 2005

Understanding Configurable FLEX Ex Analog Module Features 2-11

Table 2.4 1797-OE8 Data Formats

Data
Format

Format

Resolution Full

Output
Range

Module Data Processing

Data Table Value
(Interpretation)

Count
per mA

Analog Fault
State

0

mA as
0-20mA

0.1% of
0-20mA

0-22mA

0-22000
(0-22.000mA)

1000

min=0mA
max=22mA
hold
last=hold
50%=11mA

1

% as
0-20mA

0.2% of
0-20mA

0-22mA

0-11000
(0-110.00%)

500

min=0mA
max=22mA
hold
last=hold
50%=11mA

2

0-20mA

0-22mA

not assigned

3

unsigned
integer as
0-20mA

0.03% of
0-20mA

0-20mA

0-65,535
(0-22mA)

3276

min=0mA
max=20mA
hold
last=hold
50%=10mA

4

mA as
4-20mA

0.1% of
4-20mA

2-22mA

2000-22000
(2.000-22.000mA)

1000

min=2mA
max=22mA
hold
last=hold
50%=12mA

5

4-20mA

4-20mA

not assigned

6

4-20mA

4-20mA

not assigned

7

unsigned
integer as
4-20mA

0.03% of
4-20mA

4-20mA

0-65,535
(4-20mA)

4095

min=4mA
max=20mA
hold
last=hold
50%=12mA

8

0-20mA

0-20mA

not assigned

9

0-20mA

0-20mA

not assigned

output =

datatable

(

1,000

)

output = 20

datatable

(

10,000

)

output = 20

datatable

(

65,535

)

output =

datatable

(

1,000

)

output = 16

datatable

(

65,535

)

+ 4