Publication 1797-6.5.1 - May 2005

5-8 Calibrating Your Module

Calibrating the
Output Modules

To calibrate the 1797-OE8 module use the following general method:

1. Attach the precision current meters(s) to the module.

2. Send a message to the module to set its Output Enable bit to 1. This

enables its outputs.

3. Send a message to the module instructing it perform Zero Min and

Max Scale Coefficients.

4. Await an echo message from the module announcing that it has

performed Zero Min and Max Scale Coefficients.

5. Send a message to the module instructing it to perform Min Scale

Calibration (1mA) on the channel(s).

6. Await an echo message from the module announcing that it has

performed Min Scale Calibration.

Precision
Current
Sources

Precision
Current
Sources