Rockwell Automation 1797-OE8 FLEX Ex Analog Modules User Manual User Manual

Page 32

Advertising
background image

Publication 1797-6.5.1 - May 2005

2-16 Understanding Configurable FLEX Ex Analog Module Features

Table 2.11 Data Format - Write Words 0 and 1

Table 2.12 Error Level 0.1mA Steps

Analog Output Module (1797-OE8) Image Table Mapping

Table 2.13 Input Map (Read Words)

Bits

Description

Word 0

04 03 02 01 Data format for channels 0-3

Word 1

04 03 02 01 Data format for channels 4-7

0

0

0

0

0-22mA, w/error steps (default)

0

0

0

1

0-22mA = 0 to 110%, w/error steps

0

0

1

0

0-22mA = 0 to 104.8%, square root, w/error steps

0

0

1

1

0-22mA = 0 to 65,535, unsigned integer, w/error steps

0

1

0

0

2-22mA, w/error steps

0

1

0

1

2-22mA = -12.5% to 112.5%, w/error steps

0

1

1

0

4-22mA = 0 to 106%, square root, w/error steps

0

1

1

1

4-20mA = 0 to 65,535, unsigned integer, w/error steps

1

0

0

0

Not assigned

1

0

0

1

Not assigned

1

0

1

0

Not assigned

1

0

1

1

0-22mA = A/D count, w/fixed error

1

1

0

0

3.6-21mA = NAMUR NE 43, w/fixed error

1

1

0

1

3-21mA = -6.25 to 106.28% w/fixed error

1

1

1

0

2-22mA = -12.5 to 112.5% w/fixed error

1

1

1

1

Not assigned

Bits

Description

Word 0

13 12 11 10 9

Error level channels 0-3

Word 1

13 12 11 10 9

Error level channels 4-7

0

0

0

0

0

Disabled

0.1mA * step value = remote fault alarm threshold

Examples

Data
Format
2-22mA
-12.5 to
112.5%

0

0

1

1

1

Step value = 7, 0.1mA * 7 = 0.7mA
Remote fault alarm at -4.38% or +104.38%

0

1

1

1

1

Binary value = 15, 0.1mA * 15 = 1.5mA
Remote fault alarm at -9.38% or + 109.38%

Bit

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Word

0

Flt

Alm
ch7

Flt

Alm
ch6

Flt

Alm
ch5

Flt

Alm
ch4

Flt

Alm
ch3

Flt

Alm
ch2

Flt

Alm
ch1

Flt

Alm
ch0

Diagnostic Status

1

Res

Flg

MODULE Command Response

MODULE Response Data

Where: ch = channel

Flt Alm = Fault Alarm
Res Flg = Response Flag

Advertising