Specifications A-11

1797-OE8 CENELEC I/O Entity Parameters

Signal output (+ to -) for ch 0 to ch 7 (terminals: 0-1; 4-5; 8-9; 12-13; 17-18;
21-22; 25-26; 29-30)

Environmental Conditions

Operational Temperature
Storage Temperature
Relative Humidity
Shock

Operating
Non-Operating
Vibration

-20 to +70

o

C (-4 to +158

o

F)

-40 to +85

o

C (-40 to +185

o

F)

5 to 95% noncondensing
Tested to 15g peak acceleration, 11(+1)ms pulse width
Tested to 15g peak acceleration, 11(+1)ms pulse width
Tested 2g @ 10-500Hz per IEC68-2-6

Agency Certification

CENELEC

UL, C-UL

FM

II (1) 2G EEx ia/ib IIB/IIC T4
II (1D) (2D)
Class I Division 1 & 2 Groups A-D T4
Class I Zone 1 & 2 AEx ib/[ia] IIC T4
Class I Division 1 Groups A-D T4
Class I Zone 1 AEx ib/[ia] IIC T4

Certificates

CENELEC

DMT 00 ATEX E 042 X

UL, C-UL

UL Certificate Number 99.19699

FM

FM Certificate Number 3009806

Protection

Group

Allowed
Capacitance

Allowed
Inductance

U

o

= 21V

I

o

= 93mA

P

o

= 145mW

EEx ia

IIB

1.27

µF

10mH

IIC

188nF

3mH

If concentrated
capacitance
and/or
inductance are
available, use the
following values.

EEx ia

IIB

400nF

10mH

IIC

80nF

2mH