5-6 Calibrating Your Module

Calibrating the
Input Modules

To calibrate the 1797-IE8 or -IE8NF module use the following steps:

1. Attach the precision current source(s) to the module.

2. Send a message to the module instructing it to perform Zero Min and

Max Scale Coefficients.

3. Await an echo message from the module announcing that it has

performed Zero Min and Max Scale Coefficients.

4. Apply 1mA, (minimum scale calibration input(s),) to the module.

5. Send a message to the module instructing it to perform Min Scale

Calibration.

6. Await an echo message from the module announcing that it has

performed Min Scale Calibration.

7. Apply 21mA, (maximum scale calibration input(s),) to the module.

8. Send a message to the module instructing it to perform Max Scale

Calibration.