Publication 1797-6.5.1 - May 2005

Calibrating Your Module 5-9

7. Record the value indicated by the channel(s) precision current meter

into the appropriate channel’s(s’) data table location.

8. Send a message to the module instructing it to Accept Value in

Channel Data Word as Min Scale Calibration on the channel(s).

9. Await an echo message from the module announcing that it has

performed Accept Value in Channel(s) Data Word(s) as Min Scale
Calibration
on the channel(s).

10. Send a message to the module instructing it to perform Max Scale

Calibration (21mA) on the channel(s).

11. Await an echo message from the module announcing that it has

performed Max Scale Calibration.

12. Record the value indicated by the channel(s) precision current meter

into the appropriate channel’s(s’) data table location.

13. Send a message to the module instructing it to Accept Value in

Channel(s) Data Word(s) as Max Scale Calibration on the
channel(s).

14. Await an echo message from the module announcing that it has

performed Accept Value in Channel(s) Data Word(s) as Max Scale
Calibration
on the channel(s).

15. After all channels are calibrated, send a message to the module

instructing it to go to Commands Idle state.