Chapter summary, Chapter summary -18 – Rockwell Automation 1797-OE8 FLEX Ex Analog Modules User Manual User Manual
Page 34
 
Publication 1797-6.5.1 - May 2005
2-18 Understanding Configurable FLEX Ex Analog Module Features
Table 2.15 Data Format Control
Chapter Summary
In this chapter, we told you about the FLEX Ex system and the analog I/O 
modules, and how they communicate with programmable controllers. Move to 
Chapter 3 to learn how to install your FLEX Ex analog module.
Data
Format
Range
Resolution
Full
Range
Interpretation
Data Table
Value
Count per
mA
0
0
0
0
0-20mA
0.1% of 
0-20mA
0-22mA
0-22mA
0-22000
1000
0
0
0
1
0-20mA
0.2% of 
0-20mA
0-22mA
0-110%
0-11000
500
0
0
1
0
0-20mA
0-20mA
not assigned
0
0
1
1
0-20mA
0.03% of 
0-20mA
0-20mA
unsigned 
integer
0-65,535
3276
0
1
0
0
4-20mA
0.1% of 
4-20mA
2-22mA
2-22mA
2000-
22000
1000
0
1
0
1
4-20mA
4-20mA
not assigned
0
1
1
0
4-20mA
4-20mA
not assigned
0
1
1
1
4-20mA
0.03% of 
4-20mA
4-20mA
unsigned 
integer
0-65,535
4095
1
0
0
0
0-20mA
0-20mA
not assigned
1
0
0
1
0-20mA
0-20mA
not assigned
1
0
1
0
0-20mA
0-20mA
not assigned
1
0
1
1
0-20mA
0.28% of 
0-20mA
0-22mA
D/A count
0-8000
363
1
1
0
0
4-20mA
not assigned
1
1
0
1
4-20mA
0.16% of 
4-20mA
3-21mA
-6.25 to 
+106.25%
-625 to 
+10625
625
1
1
1
0
4-20mA
0.16% of 
4-20mA
2-22mA
-12.5 to 
+112.5%
-1250 to 
+11250
625
1
1
1
1
4-20mA
4-20mA
not assigned