Chapter summary, Chapter summary -18 – Rockwell Automation 1797-OE8 FLEX Ex Analog Modules User Manual User Manual

Page 34

Advertising
background image

Publication 1797-6.5.1 - May 2005

2-18 Understanding Configurable FLEX Ex Analog Module Features

Table 2.15 Data Format Control

Chapter Summary

In this chapter, we told you about the FLEX Ex system and the analog I/O
modules, and how they communicate with programmable controllers. Move to
Chapter 3 to learn how to install your FLEX Ex analog module.

Data
Format

Range

Resolution

Full
Range

Interpretation

Data Table
Value

Count per
mA

0

0

0

0

0-20mA

0.1% of
0-20mA

0-22mA

0-22mA

0-22000

1000

0

0

0

1

0-20mA

0.2% of
0-20mA

0-22mA

0-110%

0-11000

500

0

0

1

0

0-20mA

0-20mA

not assigned

0

0

1

1

0-20mA

0.03% of
0-20mA

0-20mA

unsigned
integer

0-65,535

3276

0

1

0

0

4-20mA

0.1% of
4-20mA

2-22mA

2-22mA

2000-
22000

1000

0

1

0

1

4-20mA

4-20mA

not assigned

0

1

1

0

4-20mA

4-20mA

not assigned

0

1

1

1

4-20mA

0.03% of
4-20mA

4-20mA

unsigned
integer

0-65,535

4095

1

0

0

0

0-20mA

0-20mA

not assigned

1

0

0

1

0-20mA

0-20mA

not assigned

1

0

1

0

0-20mA

0-20mA

not assigned

1

0

1

1

0-20mA

0.28% of
0-20mA

0-22mA

D/A count

0-8000

363

1

1

0

0

4-20mA

not assigned

1

1

0

1

4-20mA

0.16% of
4-20mA

3-21mA

-6.25 to
+106.25%

-625 to
+10625

625

1

1

1

0

4-20mA

0.16% of
4-20mA

2-22mA

-12.5 to
+112.5%

-1250 to
+11250

625

1

1

1

1

4-20mA

4-20mA

not assigned