Remote I/O Communications

8–11

Publication 2706-6.1

DL40 Plus displays communicate with PLC controllers and Remote
I/O scanners and sub-scanners as if they were a Remote I/O rack.
The DL40 Plus is compatible with all Allen-Bradley scanners that
support Remote I/O. The DL40 contains all the necessary
electronics to connect directly to the Remote I/O cable linked to a
PLC, scanner, or sub-scanner.

A sub-scanner may be used with any PLC 5/15. It allows the PLC
5/15 to communicate with up to 7 logical racks and a maximum of
16 devices, or chassis, as they are commonly called. Scanners have
both physical and logical specifications:

Physical Specifications - The maximum number of separate Remote
I/O devices (such as I/O racks, drive systems, DL40s) the scanner
can communicate with.

Logical Specifications - The maximum number of racks the scanner
can address.

Note: Different scanners have different physical and logical
specifications. See the next page.

To configure the DL40 Plus with PLC controllers you need to know:

appropriate PLC or scanner module

amount of I/O the DL40 Plus uses for different applications

number of chassis (1771 I/O racks or DL40s) and the amount of
rack I/O addressing the scanner can accommodate

For Example

A typical valid Remote I/O configuration for PLC 5/15 would be:

(4) 1/4 racks, (2) 1/2 racks and (1) full rack
Total devices = 4 + 2 + 1 = 7 devices.
This configuration is within the physical specification of
12 for the PLC 5/15.

Note: PLC 5/15 Series B, Revision H or later have partial rack
addressing. Earlier versions were limited to full racks.

4 x 1/4 racks

= 1 logical rack

2 x 1/2 racks

= 1 logical rack

1 full rack

= 1 logical rack
= 3 logical racks

This is within the

3-

rack logical limitation of the PLC 5/15. An

invalid Remote I/O configuration for a PLC 5/15 would be (8) 1/2
racks. Although 8 is less than the 12 device physical specification,
(8) x 1/2

=

4 logical racks which is greater than the PLC 5/15’s 3

rack logical specification.

Physical vs. Logical
Addressing