Triggering messages – Rockwell Automation 2706-LV2P_LV2R_LV4P_LV4R DL40 PLUS USER MANUAL User Manual

Page 105

Advertising
background image

Remote I/O Communications

8–13

Publication 2706-6.1

With the Remote I/O version of the DL40 Plus, messages are
normally triggered from a PLC connected to the DL40 Plus.
However, messages can also be triggered via the Keyboard port, the
RS-485 port or the RS-232 port.

DIP Switch 2-4 enables or disables Block Transfers.

Discrete I/O (Block Transfers disabled)

Block Transfers are ignored

amount of data sent/returned depends on rack size

Block Transfer enabled

data in Discrete I/O image tables ignored

amount of data sent/returned independent of rack size

Triggering the Same Message Consecutively

To avoid retriggering of a message via the I/O scan, the DL40 Plus
looks for changes to the message number in the Output Image or
Block Transfer Write to trigger messages. To trigger the same
message twice in a row, you must:

trigger the message the first

time.

trigger a message with a Message Number of 0.

trigger the original message a second time.

Note: In Message/Variable/Slave run mode, changing the slave
address also retriggers the same message.

Triggering Messages