Installation and Wiring

9–12

Publication 2706-6.1

When using a personal computer to upload or download application
memory to or from the DL40 Plus’s RS–485 port, use a Black Box
RS-485 converter, Model LD-485A-MP. The link from the personal
computer to the converter is an RS–232 link.
The following cable is recommended:

for an AT style computer, use an Allen–Bradley 2706-NC15.

for an XT style computer

Connect from the converter to the DL40 Plus as shown below.
Configure the converter as follows:

1. Remove cover and set the converter as a DCE device using the

XWlA jumper. This is a DIP shunt jumper.

2. Short TXA and RXA on TB1 of the converter. This should be

connected to J6, pin 5 of the DL40 Plus.

3. Short TXB and RXB on TB1 of the converter. This should be

connected to J6, pin 4 of the DL40 Plus.

4. Set switch W8 on the converter for full-duplex operation when

downloading or triggering messages via the RS–485 Port.

5. Set the RTS/CTS delay time to 5 milliseconds using jumper W9.

6. Set switch S2 to Unterminated position.

7. Replace cover.

8. Set Normal/Loopback switch on front cover to Normal.

RS-485 Port

Black Box LD485A-MP

Computer RS-232 Port

RS-485

RS-232

Shield

Signal

Ground

Term

CH-B

CH-A

Comm

Shield

E-Ground

Connecting a Programmer
to the RS-485 Port