Remote I/O Communications

8–5

Publication 2706-6.1

Handshake Bit
Tells the sender (either the DL40 Plus or the PLC) that the Image
Table (either Output or Input) was received. Handshaking is selected
by setting the Handshake DIP switch on the back of the unit. See
page 8–16 for a description of handshaking.

Hour-Minute-Second/Month-Day-Year
Each is a 2 digit BCD number with time or date data returned to a
PLC.

Length of Message List
Applies only in Message List run mode. An 8-bit binary number
between 0 and 20 indicating length of the Message List.

Message Number
(Message/Variable/Slave or Message/Variable Run Mode)
Output Image Table or Block Transfer Write - number of message to
be triggered on the DL40 Plus.

Output Image Table

Acceptable Values

1

/

4

or

1

/

2

rack (equals 12-bit)

0 to 999 in BCD format
0 to 4095 in binary format

3

/

4

or full rack (equals 16-bit)

0 to 9999 in BCD format
0 to 9999 in binary format
Note: 0 = no message triggered

Block Transfer Write

Any size rack (equals 16-bit)

0 to 9999 in BCD format
0 to 9999 in binary format
Note: 0 = no message triggered

Input Image Table or Block Transfer Read - number of message
currently running on the DL40 Plus.

Input Image Table or Block Transfer

Read

Acceptable Values

Any size rack (equals 16-bit)

0 to 9999 in BCD format
0 to 9999 in binary format
Note: 0 = no message running