Setting switch bank #1 for plc-2 controllers, A plc-2 with remote i/o, Specifying the first i/o group (plc-2) – Rockwell Automation 2706-LV2P_LV2R_LV4P_LV4R DL40 PLUS USER MANUAL User Manual

Page 146: Specifying the i/o rack size (plc-2)

Advertising
background image

DIP Switch Settings

10–2

Publication 2706-6.1

Setting Switch Bank #1 for PLC-2 Controllers

The following tables list functions and settings for Switch Bank #1
for the PLC-2 family of controllers. These tables apply to:

a PLC-2 with Remote I/O

any 1771–SN sub-scanner application (Remote I/O units)

an SLC with 1747-SN block transfer

Specifying the Rack Address of the PLC-2

I/O Rack

Switch Settings

Address

1

2

3

4

5

6

1

ON

ON

ON

ON

ON

ON

2

ON

ON

ON

ON

ON

OFF

3

ON

ON

ON

ON

OFF

ON

4

ON

ON

ON

ON

OFF

OFF

5

ON

ON

ON

OFF

ON

ON

6

ON

ON

ON

OFF

ON

OFF

7

ON

ON

ON

OFF

OFF

ON

Specifying the First I/O Group (PLC-2)

First I/O

Switch Settings

Group

7

8

0

ON

ON

2

ON

OFF

4

OFF

ON

6

OFF

OFF

Specifying the I/O Rack Size (PLC-2)

Rack

Switch Settings

Size

9

10

1/4

ON

ON

1/2

ON

OFF

3/4

OFF

ON

Full

OFF

OFF

Note: A DIP switch is ON when in the “up” position.