Installation and Wiring

9–9

Publication 2706-6.1

Connect the DL40 Plus to the scanner module with Allen–Bradley
Remote I/O cable, Catalog Number 1770–CD (Belden 9463).

Refer to Programmable Controller Wiring and Grounding Guidelines
(Publication 1770–4.1) for detailed grounding and wiring guidelines.
The User Manual or Product Data Sheet for your scanner module
also provides cabling information.

Important: When first installed, the DL40 Plus may misinterpret the
hardware configuration if the DIP switch settings are not correct. If
the FAULT indicator flashes after installation, verify the DIP switch
settings and recycle power to clear the fault.

A connector plug is provided with each DL40 Plus. Wire the
connector to the remote I/O cable as shown here.

Two

Shield

One

(Clear)

(Blue)

Remote I/O Connector
(Catalog No. 1746-RT29)