Remote I/O Communications

8–12

Publication 2706-6.1

The table below lists the number of separate chassis or devices the
scanner can support and how much I/O it can address.

Note: For any application, the total of all the I/O used by each device
(I/O rack, drive system, or DL40 Plus) connected to the cable gives
the number of full racks of I/O being supported by the scanner or
sub-scanner for that application.

Remote I/O Configuration

1771-SN

PLC

Scanners

Sub-Scanners

Processors

Physical

Logical

Physical

Logical

Mini-PLC’s

2/05

215

2/16
2/17

---

---

16 Devices

7 Racks

PLC 5/11

4 Devices

4 Racks

16 Devices

7 Racks

PLC 5/12

---

---

16 Devices

7 Racks

PLC 5/15

12 Devices

3 Racks

16 Devices

7 Racks

PLC 5/20

16 Devices

4 Racks

16 Devices

7 Racks

PLC 5/25

16 Devices

7 Racks

16 Devices

7 Racks

PLC 5/30

28 Devices

8 Racks

16 Devices

7 Racks

PLC 5/40, 5/40E

16 Devices/channel

4 Channels/scanner

15 Racks

16 Devices

7 Racks

PLC 5/60, 5/60E

16 Devices/channel

4 Channels/scanner

23 Racks

16 Devices

7 Racks

PLC 5/80, 5/80E

24 Devices/channel

4 Channels/scanner

32 Racks

16 Devices

7 Racks

PLC 5/250

32 Devices/scanner

8 Racks/Scanner

16 Devices

7 Racks

4 Scanners/processor

4 Scanners/processor

PLC 2/30

16 Devices/ channel

7 Racks total

16 Devices

7 Racks

2 Channels/scanner

PLC 3

16 Devices/channel

32 Racks (64 using

16 Devices

7 Racks

4 Channels/scanner

complimentary I/O)

PLC 3/10

16 Devices/channel

16 Racks total

16 Devices

7 Racks

4 Channels/scanner

Two of these may be Bulletin 1771 chassis.

PLC 5/15 Series B Revision H or later have partial rack addressing. Earlier versions were limited to
(3) devices.

PLC 5/20 and 5/25 Series A Revision D or later have partial rack addressing. Earlier versions were
limited to (7) devices.