Remote I/O Communications

8–3

Publication 2706-6.1

Summary of Remote I/O Run Mode Types

Feature

Message/Variable/Slave

Run Mode

Message/Variable Run

Mode

Message List Run

Mode

Bit Trigger Run Mode

Trigger messages

Trigger a message with 1 to 40 variables, depending
on rack size, trigger method, and variable type

Triggers a message list
of up to 20 messages in
Round Robin Order

Triggers a Priority
Message and up to 496
messages in Priority
and/or Round Robin
order

Triggering method

D

1/4, 1

/

2

,

3

/

4

, full rack -

Discrete I/O or Block
Transfer

D

RS-232

D

Keyboard

D

RS-485 link

D

Discrete I/O or Block Transfer

D

RS-232

D

Keyboard Port

D

RS-485 link

D

Discrete I/O or Block
Transfer

D

Keyboard (for Priority
Message only)

D

RS-485 link (for
Priority Message only)

D

RS-232

Send messages to slave
display

Slave address for each
message can be
specified with message
trigger. (Overrides
address specified as
Message Attribute)

Slave address specified as a Message Attribute

Send variables to place in
message

D

Up to 10 (16 bit) binary or (4 digit) BCD

D

Up to 20 (8 bit) ASCII

D

Up to 40 (4 bit) BCD

No

Variable types

Binary - Signed and Unsigned BCD
ASCII

Not Applicable

Handshaking

Yes

Diagnostic code sent to PLC

Yes

Message acknowledgement

Yes

Input and display of ASCII
input data (via keyboard port)

Up to 20 ASCII characters

Return ASCII input data to
PLC via Remote I/O port

D

Discrete I/O - Up to 12 characters, depending on rack size

D

Block Transfer - Up to 20 characters, independent of rack size

No

Return ASCII input data via
RS-485/RS-232 port

Up to 20 characters, independent of rack size

Put message on Historical
Events Stack

Yes